National-instruments Isolated Analog Output Module SCC-AO10 Manuel d'utilisateur Page 7

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 12
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 6
© National Instruments Corporation 7 SCC-AO10 Isolated Analog Output Module User Guide
5. Adjust the offset potentiometer on the top of the SCC-AO10 until the
voltmeter reads 0 VDC ±100 μV. The offset is now calibrated.
6. Using your software, have AO (X) output 9.9 VDC.
Adjust the gain potentiometer on the top of the SCC-AO10 until the
voltmeter reads 9.9 VDC. The gain is now calibrated.
Specifications
These ratings are typical at 25 °C unless otherwise stated.
Electrical
Number of output channels .................... One nonreferenced (floating)
Input range ............................................. ±10 V
Output range........................................... ±10 V
Current drive .......................................... ±30 mA
Gain nonlinearity.................................... 0.5% of full-scale output range
Output noise ........................................... 2.5 mV
rms
typ; 4 mV
rms
max
Bandwidth .............................................. >23 kHz
Slew rate................................................. 1 V/μs
Short circuit protection
Current ............................................ 37 mA max
Duration .......................................... Unlimited
Load impedance ..................................... 10,000 pF max
Vue de la page 6
1 2 3 4 5 6 7 8 9 10 11 12

Commentaires sur ces manuels

Pas de commentaire