Appendix C Fieldbus Parameters
©
National Instruments Corporation C-13 FieldPoint FP-3000 User Manual
LO_PRI
The priority of the low limit alarm.
LOW_CUT
With an L_TYPE of Indirect Square Root, this can be used to establish
a floor for values from the transducer. Values below this floor are
considered to be zero. The parameter can be disabled with the Low Cutoff
option in the
IO_OPTS parameter.
MANUFAC_ID
The ID of the manufacturer of the device. For National Instruments devices,
it is 0x4E4943.
MAX_NOTIFY
The maximum number of unconfirmed alarm/event notification messages
the device supports.
MEMORY_SIZE
Unused by FieldPoint.
MIN_CYCLE_T
The length of the shortest macrocycle the device supports.
MODE_BLK
Sets the operational and permitted modes of the block. Table C-9 describes
the operational and permitted modes of the block.