Vue de la page 0
FIELDPOINT
OPERATING INSTRUCTIONS
AND SPECIFICATIONS
FP-PWM-520 and
cFP-PWM-520
Eight-Channel, 5 V or 10–30 V PWM Output Module
These operating instructions describe how to install and use
the National Instruments FP-PWM-520 and cFP-PWM-520
pulse-width modulation modules (referred to inclusively as the
[c]FP-PWM-520). For details on configuring and accessing the
[c]FP-PWM-520 over a network, refer to the user manual for the
FieldPoint network module you are using.
Features
The [c]FP-PWM-520 is a FieldPoint pulse-width modulation
(PWM) output module with the following features:
Eight PWM sourcing output channels
0 to 100% duty-cycle capability with 12-bit resolution
Short-circuit protection for outputs
Outputs source 5 VDC or 10–30 VDC with user-provided
power supply
Independent configuration of the output period for each
channel from 1 to 65,535 ms in 1 ms increments
On/Off LED indicators
250 V
rms
CAT II continuous channel-to-ground isolation,
verified by 2,300 V
rms
, 5 s dielectric withstand test
–40 to 70 °C operation
Hot swappable
Vue de la page 0
1 2 3 4 5 6 ... 18 19

Résumé du contenu

Page 1 - FP-PWM-520 and

FIELDPOINT™ OPERATING INSTRUCTIONS AND SPECIFICATIONSFP-PWM-520 and cFP-PWM-520Eight-Channel, 5 V or 10–30 V PWM Output ModuleThese operating instruct

Page 2 - Installing the FP-PWM-520

FP-PWM-520 and cFP-PWM-520 10 ni.comEven though the [c]FP-PWM-520 is designed to handle applications with hazardous potentials, follow these guideline

Page 3 - Installing the cFP-PWM-520

© National Instruments Corp. 11 FP-PWM-520 and cFP-PWM-520Safety Guidelines for Hazardous LocationsThe cFP-PWM-520 is suitable for use in Class I, Div

Page 4 - Wiring the [c]FP-PWM-520

FP-PWM-520 and cFP-PWM-520 12 ni.comSpecificationsThe following specifications are typical for a range of –40 to 70 °C unless otherwise noted.Output C

Page 5

© National Instruments Corp. 13 FP-PWM-520 and cFP-PWM-520Guaranteed trip currentRevision E and later modules... 12.5 ARevision D and earlier module

Page 6 - Short-Circuit Protection

FP-PWM-520 and cFP-PWM-520 14 ni.comMechanical DimensionsFigure 5 shows the mechanical dimensions of the FP-PWM-520 installed on a terminal base. If y

Page 7 - Overcurrent Protection

© National Instruments Corp. 15 FP-PWM-520 and cFP-PWM-520Shock and VibrationThese specifications apply only to the cFP-PWM-520. NI recommends Compact

Page 8 - Status Indicators

FP-PWM-520 and cFP-PWM-520 16 ni.comElectromagnetic CompatibilityThis product is designed to meet the requirements of the following standards of EMC f

Page 9

© National Instruments Corp. 17 FP-PWM-520 and cFP-PWM-520Waste Electrical and Electronic Equipment (WEEE)EU Customers At the end of their life cycle,

Page 10

FP-PWM-520 and cFP-PWM-520 18 ni.comWhere to Go for SupportFor more information about setting up the FieldPoint system, refer to these National Instru

Page 11

© 2002–2007 National Instruments Corp. All rights reserved.373357C-01 Dec07National Instruments, NI, ni.com, and LabVIEW are trademarks of National In

Page 12 - Specifications

FP-PWM-520 and cFP-PWM-520 2 ni.comInstalling the FP-PWM-520The FP-PWM-520 mounts on a FieldPoint terminal base (FP-TB-x), which provides operating po

Page 13 - Physical Characteristics

© National Instruments Corp. 3 FP-PWM-520 and cFP-PWM-520Installing the cFP-PWM-520The cFP-PWM-520 mounts on a Compact FieldPoint backplane (cFP-BP-x

Page 14 - Environmental

FP-PWM-520 and cFP-PWM-520 4 ni.comWiring the [c]FP-PWM-520The FP-TB-x terminal base has connections for each of the eight output channels and for an

Page 15 - Hazardous Locations

© National Instruments Corp. 5 FP-PWM-520 and cFP-PWM-520Install a 2 A maximum, fast-acting fuse between the external power supply and the VSUP termin

Page 16 - Environmental Management

FP-PWM-520 and cFP-PWM-520 6 ni.comIn the ON state, the effective resistance between VOUT and VSUP causes a voltage drop between the external supply v

Page 17 - ⬉ᄤֵᙃѻક∵ᶧ᥻ࠊㅵ⧚ࡲ⊩ ˄Ё೑

© National Instruments Corp. 7 FP-PWM-520 and cFP-PWM-520• Disconnect the external power supply from the [c]FP-PWM-520.• Remove the [c]FP-PWM-520 from

Page 18 - Where to Go for Support

FP-PWM-520 and cFP-PWM-520 8 ni.comConfiguring the Output ChannelsA [c]FP-PWM-520 output channel uses period and duty-cycle settings to determine when

Page 19 - 373357C-01 Dec07

© National Instruments Corp. 9 FP-PWM-520 and cFP-PWM-520[c]FP-PWM-520, it sends initial configuration information to the [c]FP-PWM-520. After the [c]